
28
DDC Controller for Tempered Air Products
Display is hard to read.
Unit Controller Display: Hold
Esc
ESC and
ENTER at the same time, while
pressing
DOWN or
UP to adjust display contrast.
Remote Display: Hold
ALARM,
Prg
PRG, and
Esc
ESC at the same time, while
pressing
DOWN or
UP to adjust display contrast.
Remote display panel
displays “NO LINK” or
is blank.
Hold
DOWN,
UP and
ENTER for 4 seconds. Set the display address
to 32. The display requires a standard 24 AWG six conductor phone cable
connected to the unit controller.
Red alarm button is
flashing.
Press the
ALARM button to review and clear unit alarms. Enter the DATA
LOGGER menu to view previous alarms.
Controller resets itself
or is not on.
Check the supply voltage to the controller at terminals G-G0. The board requires
24VAC. Check the 24VAC transformer in the unit control center.
Menus are locked with
a password.
The factory default Manufacturer Password = 1000.
The factory default Service Password = 1000.
Temperature sensor
failure.
Check the analog input terminal block (labeled terminals B1, B2, B3, etc) for loose
wires. Disconnect temperature sensors to check sensor resistance.
Troubleshooting
NTC Temperature Sensor Chart
120
110
100
90
80
70
60
50
40
30
20
10
0
4 6 8 10 12 14 16 18 20 22 24 26 28
Temperature (ºF)
Resistance (kΩ)
®
Comentarios a estos manuales