PART #469690
DDC CONTROLLER
for ENERGY RECOVERY
Installation, Operation and Maintenance Manual
READ AND SAVE THESE INSTRUCTIONS
MANEUVERING THROUGH THE CONTROLLER
The DDC controller is located in the control panel on the energy recovery unit.
The face of the DDC controller has six buttons allowing the user to perform
various tasks such as viewing conditions or changing set points. A brief
description of the six buttons is provided. For additional details, refer to the
page references included.
Prior to accessing the controller, confirm the functions that were provided with
the unit by referencing the DDC Code shown
on the controller Start-Up screen.
The Start-Up screen appears when power is applied to the controller. The program version
and code are shown on this screen. The code shows the user what components and
functionality were provided with the unit and also dicates how the program operates. Below
is a description of the code.
Greenheck Fan Corp.
ER DDC v3.##
Code: GY2X000B
Name Heat Cool HGRH Frost Economizer
UnOccupied
Mode
Communications
GY 2 X 0 0 0 B
GFC G None – Disable X None – Disable X None – Disable X None – Disable 0 None – Disable 0 None – Unit Off 0 None X
Enable Y CW C On/Off A Timed Off 1 On/Off 1 Cycle on Room 1 Modbus M
PDx 1 stg 1 Mod B Preheat 2 Modulating 2 LON L
PDx 2 stg 2 Modulating 3 BACNet B
GFC Enable PDx 2 stg None – Disable None – Disable None – Disable None – Unit Off BACNet
Description Reference
Alarm
Indicates both visually on the controller (the button lights up) and to the Building
Management Systems (BMS) (field-wired) that something is not functioning normally.
Page 3
Up Arrow
The arrow keys allow the user to scroll through different screens and adjust
parameters.
Page 3
Down Arrow
Enter
A. In screens with adjustable parameters, pressing the Enter key moves the cursor
from the upper left corner of the screen to the parameter. The arrow keys can
then be used to adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter button.
C. To save the change, press the Enter button until the cursor moves back to the
upper left corner of the screen.
Page 3
Escape
Allows the user access to the Main Menu. The following adjustments can be made:
Page 4
• Unit Status
• Set Points
• Manual Overrides
• Analog & Digital Input/Output Setup
• Time Clock Setup
• Miscellaneous Information
• Unit On/Off
Program Allows the user access to the Program Menu
Page 17
NOTE: If this controller needs to be interfaced with a BMS (ie: Lonworks, BACnet or Modbus), please refer to page 23 for an integration points list.
Vista de pagina 0
1 2 3 4 5 6 ... 23 24

Indice de contenidos

Pagina 1 - DDC CONTROLLER

®PART #469690DDC CONTROLLER for ENERGY RECOVERY Installation, Operation and Maintenance ManualREAD AND SAVE THESE INSTRUCTIONSMANEUVERING THROUGH THE

Pagina 2 - Digital Outputs

10Access the OVERRIDES menu through the Main Menu. Scroll through the menu screens using the keys.***ACCESS DENIED***Enter Password:0000WRONG PASS

Pagina 3 - List of possible alarms

11Heater loopoverride. Heating:AUTO Loop output:000%THE USER CAN OVERRIDE THE HEATING OPERATION.This screen only appears if a Heating option was provi

Pagina 4 - MAIN MENU / ESC BUTTON

12Access the I/O SETUP menu through the Main Menu. Scroll through the menu screens using the keys.Sensor Calibration: Measure the actual temperat

Pagina 5 - UNIT STATUS MENU

13B5 Dehumidify:ON/OFFInput Status:OpenTHIS SCREEN DISPLAYS THE STATUS OF THE DEHUMIDIFICATION MODE.This screen only appears if there is a humidistat

Pagina 6 - UNIT STATUS MENU - continued

14Digital Input (ID2)Wheel pressure switch High pressure=Closed Status:OpenTHIS SCREEN DISPLAYS THE ALARM STATUS MODE OF THE ENERGY RECOVERY WHEEL PRE

Pagina 7 - SET POINTS MENU

15THIS SCREEN CAN BE LOCKED TO PREVENT TAMPERING WITH THE SETTINGS. FROM THE FACTORY, ACCESS IS NOT PASSWORD PROTECTED TO ALLOW QUICKER START-UP.To se

Pagina 8 - SET POINTS MENU - continued

16Access the MISC INFO menu through the Main Menu. Scroll through the menu screens using the keys.Greenheck Fan Corp.ER DDC1 v3.00DDC Code: GY2A21

Pagina 9

17Access the PROGRAM menu by pressing key. Scroll through the menu screens using the keys.The program button is used to setup the control loops

Pagina 10 - MANUAL OVERRIDE MENU

18Compressor Setup# of stages:2 Minimum ON:030s Minimum OFF:180sTHIS SCREEN DISPLAYS THE NUMBER OF STAGES PROVIDED WITH THE UNIT AND SHOWS THE COMPRES

Pagina 11

19Will heater be used for reheat during dehumidification?Reheat:EnableTHIS SCREEN ALLOWS THE USER TO ENABLE THE HEATER FOR REHEAT PROCESS.This screen

Pagina 12 - I/O SETUP MENU

24 VAC for Analog OutputsAnalog Output to Energy WheelAnalog Heating Output (HW or Electric)Analog Cooling Output (CW)Hot Gas Reheat Analog OutputSupp

Pagina 13 - I/O SETUP MENU - continued

20Unoccupied modesetup.Type:Cycle Supply FanSource: Input ID6Allow the dampers toopen for:10 secondsbefore starting thefans.Time delay between heating

Pagina 14

21Wheel rotation alarm delay:030s(input ID3)THIS SCREEN ALLOWS FOR THE USER TO CHANGE THE TIME DELAY UNTIL THE CONTROLLER WILL SHOW AN ALARM.This scr

Pagina 15 - TIME CLOCK MENU

22--Set Point Source--Use local set point,or BMS interface set point?:LocalUSERS CAN CHOOSE EITHER THE CONTROLLER OR THE BMS TO DETERMINE SUPPLY DISCH

Pagina 16 - UNIT ON/OFF MENU

23Carel Modbus-RTU (RS485)Network Address: 1BACnet IP / BACnet Ethernet / BACnet MSTPDevice Instance: 77000 (default)Lonworks FTT-10A Type Read (Uni

Pagina 17 - PROGRAM MENU

IOM DDC ControllerRev. 1 February 2007Copyright © 2007 Greenheck Fan Corp.WarrantyGreenheck warrants this equipment to be free from defects in materi

Pagina 18 - PROGRAM MENU - continued

3 UNIT SET POINTSThe cursor always begins in the upper left corner of the display.__Supply air low limit alarm when supply is less than: 35.0°FAlarm

Pagina 19

4Press (ENTER) to go to *SET POINTS* menu.Press (up or down) for more menu options.The SET POINTS menu allows the user to make adjustments to set poin

Pagina 20

5Access the UNIT STATUS menu through the Main Menu. Scroll through the menu screens using the keys. Screens with a dashed line border are dependen

Pagina 21

6“STATUS LINE” Hot Gas Reheat:000% Heater Control:000%“STATUS LINE”Energy recoverywheel differentialpressure is: Normal“STATUS LINE”Preheat heater: O

Pagina 22

7Access the SET POINTS menu through the Main Menu. Scroll through the menu screens using the keys.***ACCESS DENIED***Enter Password:0000WRONG PASS

Pagina 23 - (BMS to Unit signal)

8Supply Reset Limits Supply Min:055.0ºF Supply Max:090.0ºFTHIS SCREEN DISPLAYS THE MINIMUM AND MAXIMUM SUPPLY AIR TEMPERATURE.This screen only appears

Pagina 24 - Warranty

9Lockout dehumidific-ation until outsideair is:10.0ºF abovecold coil set pointTHIS SCREEN DISPLAYS THE TEMPERATURE DIFFERENCE AT WHICH THE DEHUMIDIFIC

Comentarios a estos manuales

Sin comentarios