THIS SCREEN ALLOWS THE USER TO ADJUST SCHEDULES.
This screen only appears if a Schedule was added in the screen above.
The program supports up to seven separate schedules. Each schedule will
require the user to enter a Time On, Time Off and which days the schedule is
applicable for.
Scheduler
Schedule #: #
Time On: 07:00
Time Off: 05:00
Days Enabled: MTWTFSS
THIS SCREEN ALLOWS THE USER TO ENABLE THE MORNING WARM-UP SEQUENCE AND
THE DIFFERENTIAL REQUIRED TO ALLOW THE SEQUENCE TO OCCUR.
This screen only appears if Unoccupied Tempering is available.
The morning warm-up sequence calculates the time required to temper the space
to the occupied set point prior to occupancy. This sequence is limited between 10
to 60 minutes. The controller will re-evaluate the heating and cooling rate daily to
continually adjust to the changing climate.
Morning Warm-up
Morning Warmup Off
Temperature Diff: 2.0°F
THIS SCREEN ALLOWS THE USER TO SET HOLIDAY DATES (IF ENABLED).
This screen only appears if Holidays are enabled.
The internal time clock will go into unoccupied mode as long as the date is equal
to the holiday date (always a 24 hour period).
Holiday #1
Month: MM
Day: DD
Unoccupied for 24 hrs
THIS SCREEN ALLOWS THE USER TO ADD THE NUMBER OF UNOCCUPIED SCHEDULES
AND HOLIDAYS.
The Number of Schedules corresponds to the number of unoccupied periods the
user wishes to add. By setting the number of schedules to a value greater than
zero, the unoccupied mode will automatically be set to time clock.
A holiday is a single occurrence in which you would like the unit to be unoccupied
for 24 hours. A maximum of 15 holidays can be set. Holidays must be
reconfigured each year.
Scheduler
Number of schedules: 0
Holidays
Holiday = unoccupied mode
for 24 hours.
Number of Holidays: 0
To manually control I/O values, go to the Service menu > Overrides.
Similar screens appear for all controller inputs and outputs.
Your controller may not utilize all equipped of the inputs and outputs
shown. See unit wiring diagram for your specific configuration.
Analog Input
Outside Temperature
Input B01: 75.0°F
D. Input/Output
The Input/Output menu allows the user to quickly view the status of the controller
inputs and outputs.
E. Data Logger
THIS SCREEN IS AN EXAMPLE OF A RECORDED ALARM.
The unit conditions are displayed for past alarm events. The date, time,
temperatures and unit status are recorded.
To clear recorded alarms, press
Prg
and
Esc
simultaneously.
13:21:04 MM/DD/YY
OA TEMP SENSOR
Outside Air T: -623.3
Discharge T: 52.8
Cold Coil T: 55.9
Room T: 72.5
SYS ON-HEATING
The Data Logger menu allows the user to view up to 100 past alarms.
C. Clock/Scheduler
The Clock/Scheduler menu allows the user to view and alter the time and date.
The user can also add up to seven schedules for occupancy requirements.
THE CLOCK SCREEN ALLOWS THE USER TO ADJUST THE TIME AND DATE.
Set Date & Time
Day: Monday
Date: MM/DD/YY
Hour: 15:30
22
DDC Controller for Tempered Air Products
®