THIS SCREEN ALLOWS THE USER TO OVERRIDE THE HEATING OPERATION.
This screen only appears if a heating operation was provided with the unit.
When the Heating Control is in the MANUAL mode, use the arrow buttons to vary
the heating output.
Electric Heater: The Heater Control % is proportional to the 0-10 VDC signal
being sent to the SCR controller, located in the electric heater control center.
0% Heating = 0 VDC - 0 kW output
100% Heating = 10 VDC - Max kW output
Hot Water: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the heating control valve (BY OTHERS).
0% Heating = 0 VDC
100% Heating = 10 VDC
Indirect Gas: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the indirect gas furnace controller, located in the indirect gas control
center. The first stage is on at 1% Heater Control. The furnace will then modulate
proportionally from minimum to maximum capacity. The furnace is subject to
minimum On/Off times and Heating Lockouts.
0% = 0 VDC – OFF
1% = 0 VDC – MINIMUM TURNDOWN ENABLED
1 - 100% = 0 - 10 VDC = FURNACE MODULATION
Heat Pump: The Heating % displays compressor engagement as a percent. The
compressors are subject to the minimum On/Off times and Heating Lockouts.
Compressors engage in sequence as described in the Compressor Staging
screen in the Manufacturer > Factory Settings menu.
Heating Override
Heating Control: Auto
Heating: 100%
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE COOLING OPERATION.
This screen only appears if a cooling operation was provided with the unit.
When the Cooling Control is in the MANUAL mode, use the arrow buttons to vary
the cooling output.
Chilled Water: The Cooling % is directly proportional to the 0 - 10 VDC output
signal.
0% Cooling = 0 VDC; 100% Cooling = 10 VDC
Packaged Cooling and Heat Pump: The Cooling % displays compressor
engagement as a percent. The compressors are subject to the minimum
On/Off times and Heating/Cooling Lockouts. Compressors engage in sequence
as described in the Compressor Staging screen in the
Manufacturer > Factory Settings menu.
Cooling Override
Cooling Control: Auto
Cooling: 100%
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE ENERGY RECOVERY WHEEL
PREHEATER.
This screen only appears if an electric preheat frost control was provided with the
unit.
Wheel Preheat Override
Energy Recovery Wheel
Preheat Control: Auto
Preheater: OFF
THIS SCREEN ALLOWS THE USER TO OVERRIDE THE ENERGY WHEEL OPERATION.
This screen only appears if the unit is equipped with a VFD operated energy wheel.
When the Wheel Control is in the MANUAL mode, use the arrow buttons to alter
the wheel %. This is directly proportional to a 0 - 10 VDC signal being sent to the
energy wheel VFD.
Energy Wheel Override
Wheel Control: Auto
Wheel: 100%
24
DDC Controller for Tempered Air Products
®