THIS SCREEN ALLOWS THE USER TO VIEW AND CHANGE THE CONTROLLER PLAN
ADDRESS.
A pLAN (pCO Local Area Network) is a Carel® proprietary local area network,
allowing the user to connect multiple controllers to one remote display panel.
Each controller on a pLAN must have a unique address.
This address is only applicable for units connected on a pLAN. For BACnet,
LonWorks or Modbus parameters, go to Service > BMS Config.
Controller pLAN Setup
Current pLAN Addr: 1
New pLAN Addr: 1
pLAN Port
Protocol: pLAN
THIS SCREEN DISPLAYS AND ALLOWS ADJUSTMENT OF THE UNIT CODE.
This code is set from the factory to operate the components selected with the
unit. When troubleshooting, refer to the wiring diagram sent with the unit (located
on the control center door) to verify the Unit Code is correct. The code will be
listed on the wiring diagram. If changes to the setup code are required, save the
configuration by changing Save Config to YES.
Unit Code
Select DDC configuration
code here.
Code: GWY1X000XXXX
Save Config: No
THIS SCREEN ALLOWS THE USER TO ENABLE ADDITIONAL I/O POINTS.
Unit I/O expansion requires the installation of a pCOe and Field Card. See
page 34 for more information.
Enabling the I/O expansion allows the user to add the following points for
monitoring:
• Four analog inputs (0/1vdc, 0/5vdc, 0/20mA, 4/20mA, NTC Temp)
• One analog output (0/10vdc)
• Four digital inputs
• Four digital outputs
The additional I/O points available on the pCOe expansion module allow the user to
monitor and control the additional points over the BMS and user display.
Unit Expansion I/O
Enable Expansion: No
H. Manufacturer
a. Configuration
Configuration menu allows the user to change the setup code for the unit, enable
Scheduling, Holidays, expansion I/O and change Field Card settings. Users are
welcomed to enable Scheduling and Holidays. However, code changes and
expansion I/O enabling are to be done under factory advice only!
28
DDC Controller for Tempered Air Products
®