“STATUS LINE”
Hot Gas Reheat:000%
Heater Control:000%
“STATUS LINE”
Energy recovery
wheel differential
pressure is: Normal
“STATUS LINE”
Preheat heater: OFF
End of status menu
THIS SCREEN DISPLAYS THE CURRENT REHEAT AND HEAT OPERATION OF THE UNIT.
Hot Gas Reheat only appears if provided with unit.
Hot Gas Reheat operation is on/off control displayed as a percent.
100% is ON and 000% is OFF
To override: ‘MANUAL OVERRIDE’ menu >Hot Gas Reheat Override
For Modulating Hot Gas Reheat Control:
000% is OFF and 001% HGRH is ON and the airflow damper is modulating
between 4 VDC and 10 VDC.
Heater Control displays the real-time percent heater output and is directly proportional
to a 0-10 VDC signal provided by the discharge temperature sensor.
To override: ‘MANUAL OVERRIDE’ menu >Heating Loop Override
Electric Heater: The Heater Control % is directly proportional to a 0-10 VDC signal
being sent to the SCR controller in the electric heater’s control center.
000% = 0 VDC = 0 kW output
100% = 10 VDC = Maximum kW output
Indirect Gas Furnace: The Heater Control % is directly proportional to a 0-10 VDC
signal being sent to the indirect gas furnace control board. The first stage is full ON at a
1% Heater Control. Once the Heater Control reaches 50%, the second stage modulates
between 50% and 100% output.
001 – 049% First stage: ON, Second stage: OFF
050 – 100% First stage: ON, Second stage: Modulating between
50% and 100% output
Hot Water Heater: The heating control valve (supplied by others) can either be 0-10 VDC
or 2-10 VDC depending upon what valve is installed. The user may have to adjust the
‘I/O SETUP’ menu so that a 0-100% heating correlates with a 2-10 VDC signal (0-10 VDC
is default).
To adjust: ‘I/O SETUP’ menu >Analog Output Y2
THE UNIT CONTAINS A WHEEL PRESSURE DROP SENSOR TO INDICATE WHETHER
THE PRESSURE ACROSS THE WHEEL IS NORMAL OR HIGH.
This screen only appears if a frost control method was provided.
A status of High is an indication of frost accumulation. The pressure set point is
adjustable on the wheel pressure switch.
THIS SCREEN INDICATES WHETHER THE ELECTRIC PREHEAT FROST CONTROL IS ON
OR OFF.
This screen only appears if Electric Preheat frost control was provided.
To override: ‘MANUAL OVERRIDE’ menu >Energy Recovery Wheel Preheater
UNIT STATUS MENU - continued
THIS SCREEN DISPLAYS THE COOLING CONTROL AS A PERCENTAGE (CONTINUED)
The Compressor line indicates which compressor is ON
1 First compressor
2 Second compressor
1 2 Both compressors
To override: ‘MANUAL OVERRIDE’ menu >Cooling Loop Override
“STATUS LINE”
Cooling Control:000%
Compressor: ##