15
THIS SCREEN CAN BE LOCKED TO PREVENT TAMPERING WITH THE SETTINGS.
FROM THE FACTORY, ACCESS IS NOT PASSWORD PROTECTED TO ALLOW QUICKER
START-UP.
To set the password, go to the ‘PROGRAM’ menu by pressing the button. Once
there, scroll down until you arrive at the Change Password screen. The ‘Level 1
password protects the ‘TIME CLOCK’ menu.
CLOCK
hr:min:sec
(Day of week)
mm/dd/yyyy
THE CLOCK SETUP MENU ALLOWS THE USER TO ADJUST THE TIME, DATE, AND
OCCUPIED/UNOCCUPIED MODE SETTINGS.
User can also override the current occupied/unoccupied mode for a designated period
of time.
Time/Date/Day Setup
Press ENTER to reset
the internal clocks
time, date & day
Reset clock
Time-00:00:00
Date: 00/00/00 (m/d/y)
Day-NA
Set the time, date & day here. All three must be
set/reset at the same time. When the cursor is in the
upper left corner, press up or down to return to the
clock menu.
IMPORTANT! User must select one of the three options for the Source in the
Unoccupied mode setup screen in the ‘PROGRAM’ menu. The Source represents the
means by which Occupied and Unoccupied modes are determined.
Option 1: Input ID6 – typically used with a remote time clock (Default)
Option 2: BMS – can be overridden by a separate input to ID6
Option 3: Internal Time Clock – can be overridden by a momentary input to ID6
Occ-Unocc Override
Current Mode:Occ
Override Time:060min
Override:No
CURRENT MODE DISPLAYS WHETHER THE UNIT IS IN OCCUPIED MODE OR
UNOCCUPIED MODE.
(OCC = OCCUPIED, UNOCC = UNOCCUPIED)
This screen will only appear if the Occupied/Unoccupied ID6 function has been set
to ‘ON’ in the PROGRAM menu under Binary Input Enables.
The controller will allow the user to override from Unoccupied to Occupied mode, but
not vice versa. This can be performed by changing this screen to Yes, or it can also
be done through a momentary 24 VDC input to terminal ID6. After the Override Time
expires, the clock returns to the 7-day schedule.
Enable Occ/Unocc
Mon:Yes Tue:Yes Fri:Yes
Wed:Yes Thu:Yes Sat:Yes
Sun:Yes
The following screens only appear if Option 3, the Internal Time Clock function, has been enabled in the Program
Menu.
THIS SCREEN ALLOWS THE USER TO ENABLE/DISABLE UNOCCUPIED MODE FOR
EACH DAY OF THE WEEK.
Selecting ‘No’ means the unit will operate in an Occupied mode only.
Selecting ‘Yes’ means the unit will operate in an Occupied mode and an Unoccupied
mode.
Occupied Unoccup
Mon 06:00 18:00
Tue 06:00 18:00
Wed 06:00 18:00
Enter the desired Occupied/Unoccupied start times for each day (24 hour time scale).
Occupied Unoccup
Thu 06:00 18:00
Fri 06:00 18:00
Enter the desired Occupied/Unoccupied start times for each day (24 hour time scale).
Access the
CLOCK SETUP menu through the Main Menu. Scroll through the menu screens using the keys.
***ACCESS DENIED***
Enter Password:0000
WRONG PASSWORD
TIME CLOCK MENU