Unoccupied mode
setup.
Type:Cycle Supply Fan
Source: Input ID6
Allow the dampers to
open for:10 seconds
before starting the
fans.
Time delay between
heating, cooling, &/or
economizer modes.
Delay:600s
THIS SCREEN ALLOWS FOR THE USER TO ADJUST THE DELAY TIME BETWEEN
MODES.
This time delay prevents short-cycling between heating, cooling and/or economizer
modes.
THIS SCREEN DISPLAYS WHAT THE UNIT WILL DO IN UNOCCUPIED MODE.
Setting the Type to Cycle Supply Fan will engage the unit to maintain space
temperature. However, the room suppy temp sensor must be wired between B4 and
BC4 on the controller. If desired, the Source offers three options that can be used to
operate unoccupied/occupied modes:
Option 1: Input ID6 – typically used with a remote time clock (Default)
Option 2: BMS – can be overridden by a separate input to ID6
Option 3: Internal Time Clock – can be overridden by a separate input to ID6
Without the room supply temp sensor, the Type will say Unit Off, and thus the unit will
be off during unoccupied mode.
THIS SCREEN ALLOWS FOR THE USER TO PROGRAM THE TIME FOR THE DAMPERS
TO OPEN PRIOR TO THE FAN ENGAGING.
This allows for a smoother startup of the system and prevents the fans from having
to overcome the higher pressures when dampers are just beginning to open. Since
dampers have a slow reaction time, the default is 10 seconds which allows enough time
for them to fully open.
Fan/airflow proving
alarm delay:030s
(inputs ID1 & ID5)
THIS SCREEN ALLOWS FOR THE USER TO DELAY AN ALARM SIGNAL FROM THE FAN
AIRFLOW PROVING SWITCH WHICH SHUTS THE UNIT DOWN.
Since the unit is only part of a complete system, the airflows may momentarily change
(ie. If a downstream damper closes). This delay is intended to prevent false alarms (the
factory recommends that at least 30 seconds be programmed into the controller).
Time delay between
starting of supply
& exhaust fans.
Fan delay:005s
Also, the exhaust fan engages first, allowing the wheel to see space temperature
conditions prior to the supply fan engaging. This allows the energy recovery wheel
the opportunity to provide maximum preconditioning of the outdoor air. This also
minimizes the potential of extreme outdoor air temperatures being supplied to the
space prior to the cooling and or heating sections engaging.
PROGRAM MENU - continued
THE TIME DELAY BETWEEN THE STARTING OF THE SUPPLY AND EXHAUST FANS
THAT REDUCES THE STARTUP AMP DRAW OF THE UNIT.