21
Wheel rotation alarm
delay:030s
(input ID3)
THIS SCREEN ALLOWS FOR THE USER TO CHANGE THE TIME DELAY UNTIL THE
CONTROLLER WILL SHOW AN ALARM.
This screen appears whether the wheel rotation alarm was provided or not. If
provided, there will be a wire in ID3 on the controller.
Similar to the Fan/airflow proving switch alarm, the Wheel rotation alarm delay allows
time to elapse prior to the controller showing an alarm. The delay prevents a false
alarm from occurring if the sensor does not pickup the wheel rotation for a second or
two.
Communications Setup
Press ENTER to setup the
communication parameters
The communications setup allows the user to program the type of BMS system
(BACnet, LonWorks, pcoWEB, or MODBUS), and where required, the Identification
# and Baud numbers needed to operate the controller. Screens displaying the
communication options available with this unit are shown.
Communications Setup
Comm Type:None
Communications Setup
Comm Type:BACnet
Communications Setup
Comm Type:LonWorks
Communications Setup
Comm Type:pcoWEB
Communications Setup
Comm Type:PlantVisor
Identification #:001
Communications Setup
Comm Type:Modem
Identification #:001
Communications Setup
Comm Type:MODBUS
Identification #:001
Baud:9600
PROGRAM MENU - continued