17
Access the PROGRAM menu by pressing key. Scroll through the menu screens using the keys.
The program button is used to setup the control loops for economizer, defrost, heating, cooling, and reheat
along with defaults for staging, supply reset, time delays, occupied mode, communications, set point source,
temperature scale, and changing passwords. Adjustments to these parameters should be performed by a
qualified technician. (A Level 2 password must be entered to alter any of the factory programming; factory
default is 9998).
THIS SCREEN CAN BE LOCKED TO PREVENT TAMPERING WITH THE SETTINGS.
FROM THE FACTORY, ACCESS IS NOT PASSWORD PROTECTED TO ALLOW QUICKER
START-UP.
To set the password, go to the ‘PROGRAM’ menu by pressing the button. Once
there, scroll down until you arrive at the Change Password screen. The ‘Level 2’
password protects the ‘Program’ menu.
***ACCESS DENIED***
Enter Password:0000
WRONG PASSWORD
Factory Setup
Consult factory
before altering
Economizer Controller
Integration:300s
Control Band:20ºF
THIS SCREEN ALLOWS THE INTEGRATION TIME FOR THE PI CONTROL OF THE
ECONOMIZER AND THE TEMPERATURE BAND AROUND THE SUPPLY SET POINT TO
BE ADJUSTED.
This screen will only appear if an Economizer mode was selected with the unit.
This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Supply set pt ± Band. ie: 50° F ± 20° F
Economizer Setup
Econo on/off times
Minimum ON:300s
Minimum OFF:300s
THIS SCREEN ALLOWS ADJUSTMENT FOR THE MINIMUM ON/OFF TIMES FOR THE
ECONOMIZER.
This screen only appears if ON/OFF economizer was provided with the unit.
These minimum ON and OFF times prevent the energy wheel motor from short cycling
during economizer mode.
Supply fan cycling
defrost setup.
Fan off time:005min
Fan on time:030min
THIS SCREEN DISPLAYS THE ON/OFF FAN CYCLE TIMES FOR THE TIMED
EXHAUST FROST CONTROL AND ALLOWS THE USER TO ADJUST THESE
PARAMETERS.
This screen only appears if Timed Exhaust Frost Control was provided with the unit.
These ON and OFF times prevent the buildup of frost when the unit is in Timed Exhaust
frost control mode.
Cooling Controller
Integration:300s
Band:20ºF
THIS SCREEN DISPLAYS THE INTEGRATION TIME FOR THE PI CONTROL OF THE
COOLING MODE, AND THE TEMPERATURE BAND AROUND THE SUPPLY SET POINT.
This screen only appears if a Cooling option was provided with the unit.
This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Supply set pt ± Band. ie: 50° F ± 20° F
PROGRAM MENU